Three-Phase Power Calculator (kW, kVA, Amps)

Work out three-phase kW, kVA and kVAR from current readings, or the line current a motor or machine will draw.

Real power
Apparent power
Reactive power

Runs entirely in your browser. Nothing you enter is sent anywhere.

How it works

For a balanced three-phase load, apparent power is √3 × line voltage × line current. Real power, the part that does work, is that times the power factor. Reactive power is the rest, which circulates without doing useful work.

To size cables and breakers from a motor's output rating, divide by both power factor and efficiency to get the electrical input current.

S (VA) = √3 × V_L × I_L
P (W) = S × PF
Q (VAR) = S × sin(arccos PF)
I = P_out / (√3 × V_L × PF × η)

Worked example

A load on a 415 V supply draws 20 A per line at power factor 0.85. Apparent power is √3 × 415 × 20 = 14.38 kVA, real power 12.22 kW and reactive power 7.57 kVAR.

Frequently asked questions

Why multiply by √3?

In a three-phase system the line-to-line voltage is √3 times the phase voltage, and the three phases together deliver √3 × V_line × I_line volt-amperes.

What power factor should I assume?

Use the nameplate value if you have it. Induction motors are typically around 0.8–0.9 at full load and lower when lightly loaded.